Kohler 12RESV
KOHLER Home Generators, Home standby
- Running
- 11,000 W
- Starting
- n/p
- Weight
- 433 lb
The Kohler 14RCA supplies 12,000 W running on natural gas and 14,000 W on LP, with no published starting figure. It runs a refrigerator, a window AC (12,000 Btu) and LED lights together. It starts a well pump (1 HP), a central AC (3 ton) and a sump pump (1/2 HP), each on its own.
Each setup has every appliance on at once, with the largest motor starting on top of the rest. Running and starting watts for each appliance are the medians from sampled real models; see the appliance chart.
| Scenario | Appliances, all on at once | Running needed W | Peak as the largest motor starts W | Result | Limited by |
|---|---|---|---|---|---|
| Storm outage | refrigerator, furnace blower, sump pump (1/2 HP), LED lights, TV, wi-Fi router, phone charger x2 | 2,741 | 3,955 | Runs | nothing |
| RV weekend | RV air conditioner, microwave, LED lights, TV, phone charger x2 | 3,379 | 6,283 | Runs | nothing |
| Job site | circular saw (7-1/4 inch), air compressor, LED lights, phone charger | 3,167 | 9,329 | Runs | nothing |
| Camping | mini fridge, coffee maker, LED lights, phone charger x2 | 1,117 | 1,587 | Runs | nothing |
| CPAP night | CPAP machine, LED lights, phone charger | 201 | 201 | Runs | nothing |
Each appliance checked alone against 12,000 W running and 12,000 W (no starting figure published, so its running watts).
A standby generator runs as long as its gas supply lasts. These are the maker's printed fuel consumption figures.
| Fuel | Load | Fuel use | Unit | Source |
|---|---|---|---|---|
| natural gas | 100% | 193 | ft3/h | techcomm.rehlko.com |
| natural gas | 75% | 163 | ft3/h | techcomm.rehlko.com |
| natural gas | 50% | 124 | ft3/h | techcomm.rehlko.com |
| natural gas | 25% | 93 | ft3/h | techcomm.rehlko.com |
| LP (propane) | 100% | 81 | ft3/h | techcomm.rehlko.com |
| LP (propane) | 75% | 75 | ft3/h | techcomm.rehlko.com |
| LP (propane) | 50% | 60 | ft3/h | techcomm.rehlko.com |
| LP (propane) | 25% | 45 | ft3/h | techcomm.rehlko.com |
A home standby generator has no outlets on the unit. It connects to the house wiring through a transfer switch installed by a licensed electrician. Output: 120/240 V.
Readings are compared only when both models were measured at the same distance and load.
| Sibling | Measured | This model dBA | Sibling dBA |
|---|---|---|---|
| Kohler 20RCA | 23 ft and 0% load | 63 | 66 |
The current generators nearest on running watts, fuel, weight, noise and price. The rule is on the methodology page.
KOHLER Home Generators, Home standby
Briggs & Stratton Energy Solutions, Home standby
KOHLER Home Generators, Home standby
| Spec | Value | Printed as | Document | Checked |
|---|---|---|---|---|
| Running watts on natural gas | 12,000 W | Generator Ratings, Standby Ratings, Natural Gas kW/kVA: 12/12 (2F5, 120/240 V, 1 phase, 60 Hz) | techcomm.rehlko.com (spec sheet pdf) | |
| Starting watts on natural gas | not published | no source | ||
| Running watts on propane | 14,000 W | Generator Ratings, Standby Ratings, LPG kW/kVA: 14/14 (2F5, 120/240 V, 1 phase, 60 Hz) | techcomm.rehlko.com (spec sheet pdf) | |
| Starting watts on propane | not published | no source | ||
| Weight | 452.5 lb (205.3 kg) | Generator Set Dimensions and Weights, Shipping Weight, 14RCA Generator Set: 205.3 kg (452.5 lbs.) | techcomm.rehlko.com (spec sheet pdf) | |
| Noise at 23 ft and 0% load | 63 dBA | Generator Set Sound Data: 63 dB(A) during weekly engine exercise | techcomm.rehlko.com (spec sheet pdf) | |
| Noise at 23 ft (load not stated) | 69 dBA | Generator Set Sound Data: 69 dB(A) during full-speed generator diagnostics and normal operation | techcomm.rehlko.com (spec sheet pdf) | |
| Warranty | 5 years or 2,000 hours, premium limited standby warranty covering parts, labor and travel for the full period | Premium 5-yr/2000-hr Limited Warranty Included | techcomm.rehlko.com (spec sheet pdf) | |
| List price (MSRP) | $5,098 | Starting at $5,098 MSRP* | kohlerhomeenergy.rehlko.com (product page html) | |
| Natural gas use at 100% load | 193 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, Natural Gas, 100% load: 5.4 (193) | techcomm.rehlko.com (spec sheet pdf) | |
| Natural gas use at 75% load | 163 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, Natural Gas, 75% load: 4.7 (163) | techcomm.rehlko.com (spec sheet pdf) | |
| Natural gas use at 50% load | 124 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, Natural Gas, 50% load: 3.5 (124) | techcomm.rehlko.com (spec sheet pdf) | |
| Natural gas use at 25% load | 93 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, Natural Gas, 25% load: 2.6 (93) | techcomm.rehlko.com (spec sheet pdf) | |
| Propane use at 100% load | 81 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, LPG, 100% load: 2.3 (81) | techcomm.rehlko.com (spec sheet pdf) | |
| Propane use at 75% load | 75 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, LPG, 75% load: 2.1 (75) | techcomm.rehlko.com (spec sheet pdf) | |
| Propane use at 50% load | 60 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, LPG, 50% load: 1.8 (60) | techcomm.rehlko.com (spec sheet pdf) | |
| Propane use at 25% load | 45 ft3/h | Operation Requirements, Fuel Consumption, m3/hr. (cfh) @ 60Hz, LPG, 25% load: 1.2 (45) | techcomm.rehlko.com (spec sheet pdf) |
Yes. A refrigerator draws about 780 W running, the median of 3 sampled models, and needs 1,200 W to start by the generator maker's chart. The Kohler 14RCA supplies 12,000 W running with no published starting figure, leaving 11,220 W running to spare. Other loads on at the same time share that margin.
A standby generator runs as long as its gas supply lasts, so it has no tank runtime. At half load the Kohler 14RCA burns 124 ft3/h of natural gas and 60 ft3/h of LP, by the maker's fuel table. At full load it burns 193 ft3/h of natural gas and 81 ft3/h of LP.
The maker prints 63 dBA at 23 ft and 0% load and 69 dBA at 23 ft (load not stated) for the Kohler 14RCA. This site compares noise only between models measured at the same distance and load. The quietest figure comes from the maker's spec sheet, checked Oct 7, 2026.
No. The Kohler 14RCA is a home standby generator with no outlets on the unit. It connects to the house wiring through a transfer switch installed by a licensed electrician. It supplies 12 kW on natural gas at 120/240 V.
The Kohler 14RCA is a 15,000 watt class home standby generator: 12 kW on natural gas and 14 kW on LP, with no published starting figure. Size classes here follow the highest running figure on any fuel. It weighs 452.5 lb (205.3 kg). It runs at 120/240 V.