Champion 6500W Dual Fuel Inverter 201532
Champion Power Equipment, Dual fuel inverter
- Running
- 5,250 W
- Starting
- 6,500 W
- Weight
- 105.4 lb
A heat pump is rated 3,456 W on the nameplate, the median of 5 sampled models. Champion's generator chart lists 3,000 to 3,500 W running. Sizing uses 6,000 W to start: the top of Champion's starting band, as no maker prints one. The smallest size that covers it alone is 5,500 W.
| Figure | Value | Where it comes from |
|---|---|---|
| Rated draw (nameplate) | 3,456 W | Median of 5 sampled models: printed watts, or printed amps x 240 V. A nameplate figure is a maximum rating. |
| Typical running (generator maker's chart) | 3,000 to 3,500 W | Champion generator wattage chart |
| Starting (generator maker's chart) | 5,000 to 6,000 W | Champion generator wattage chart |
| Inrush (LRA x 240 V) | 22,440 W | Highest locked rotor amps on the sampled sheets times the voltage. A split-second stalled-rotor figure; not used for sizing. |
| Starting watts for sizing | 6,000 W | Used because no sampled maker prints a surge, so it is the top of Champion's starting band. |
| Amps at 240 V | 14.4 A | Rated draw divided by 240 V. |
What was sampled: 2 to 3 ton split-system heat pump outdoor unit, 208/230 V single phase, single-stage, R-454B or R-32.
Each row is one real model and the figure its maker prints. Computed watts are printed watts, or printed amps times 240 V when the maker prints amps only.
| Printed as, document, checked | ||||||
|---|---|---|---|---|---|---|
| Goodman | GLZS4BA2410 | 8.2 | not published | 41.2 | 1,968 | RLA, goodmanmfg.com, checked |
| Goodman | GLZS4BA3610 | 16.4 | not published | 88 | 3,936 | RLA, goodmanmfg.com, checked |
| Carrier | 27SCA5 size 36 | 14.4 | not published | 86 | 3,456 | COMPR RLA, shareddocs.com, checked |
| Lennox | ML14KP1-024-230 | 10.3 | not published | 60.2 | 2,472 | Compressor Rated load amps, lennox.com, checked |
| Lennox | ML14KP1-036-230 | 16.7 | not published | 93.5 | 4,008 | Compressor Rated load amps, lennox.com, checked |
The smallest listed size that covers 3,456 W running and 6,000 W starting on its own is 5,500 W. It runs on 240 V, so the generator needs a 240 V outlet.
The smallest current generators in our data that run it alone:
Champion Power Equipment, Dual fuel inverter
Westinghouse Outdoor Power Equipment, Open frame
Westinghouse Outdoor Power Equipment, Open frame
Each size is treated as its own running watts, with a starting figure from the median surge of current generators that size. Each question links to the full list for that size.
| Question | Generator running W | Generator starting W | Answer |
|---|---|---|---|
| Will a 2,000 watt generator run a heat pump? | 2,000 | 2,545 | No, too many running watts |
| Will a 3,500 watt generator run a heat pump? | 3,500 | 4,375 | No, cannot start it |
| Will a 5,000 watt generator run a heat pump? | 5,000 | 5,500 | No, cannot start it |
| Will a 7,500 watt generator run a heat pump? | 7,500 | 9,388 | Yes, with a 240 V outlet |
Each row adds one more appliance. On this page a 3,500 W generator supplies 3,500 W running and 4,375 W starting.
| Running at once | Running total W | Peak at the largest start W | Runs |
|---|---|---|---|
| Heat pump | 3,456 | 6,000 | No, cannot start it |
| Heat pump + LED lights | 3,465 | 6,009 | No, cannot start it |
| Heat pump + LED lights + phone charger | 3,485 | 6,029 | No, cannot start it |
| Heat pump + LED lights + phone charger + TV | 3,704 | 6,248 | No, too many running watts |
| Heat pump + LED lights + phone charger + TV + refrigerator | 4,484 | 7,028 | No, too many running watts |
2,472 W running 4,500 W starting
3,240 W running 6,000 W starting
5,376 W running 8,000 W starting
750 W running 1,600 W starting
1,035 W running 2,400 W starting
445 W running 1,200 W starting
710 W running 2,400 W starting
| Spec | Value | Printed as | Document | Checked |
|---|---|---|---|---|
| Goodman GLZS4BA2410: rated amps | 8.2 A | RLA | goodmanmfg.com (spec sheet pdf) | |
| Goodman GLZS4BA2410: locked rotor amps | 41.2 A | LRA | goodmanmfg.com (spec sheet pdf) | |
| Goodman GLZS4BA3610: rated amps | 16.4 A | RLA | goodmanmfg.com (spec sheet pdf) | |
| Goodman GLZS4BA3610: locked rotor amps | 88 A | LRA | goodmanmfg.com (spec sheet pdf) | |
| Carrier 27SCA5 size 36: rated amps | 14.4 A | COMPR RLA | shareddocs.com (spec sheet pdf) | |
| Carrier 27SCA5 size 36: locked rotor amps | 86 A | COMPR LRA | shareddocs.com (spec sheet pdf) | |
| Lennox ML14KP1-024-230: rated amps | 10.3 A | Compressor Rated load amps | lennox.com (spec sheet pdf) | |
| Lennox ML14KP1-024-230: locked rotor amps | 60.2 A | Locked rotor amps | lennox.com (spec sheet pdf) | |
| Lennox ML14KP1-036-230: rated amps | 16.7 A | Compressor Rated load amps | lennox.com (spec sheet pdf) | |
| Lennox ML14KP1-036-230: locked rotor amps | 93.5 A | Locked rotor amps | lennox.com (spec sheet pdf) |
The 5 models we sampled print a median of 3,456 W on the nameplate. A nameplate figure is the maximum the maker rates, not the average while running. The Champion generator chart lists 3,000 to 3,500 W as typical running watts. Plan for 6,000 W when it starts.
At 240 V, 3,456 W works out to 14.4 A. That is the median nameplate draw divided by 240 V. A heat pump draws from a 240 V circuit, so a generator needs a 240 V outlet to run it. Locked rotor amps put the split-second inrush near 22,440 W, a figure not used for sizing.
The smallest listed size that covers a heat pump on its own is 5,500 W. That covers 3,456 W running and 6,000 W starting. Anything else running at once adds to that. The smallest current generator in our data that runs it alone is the Champion 6500W Dual Fuel Inverter 201532 at 5,250 W running.
We size a heat pump at 6,000 W to start, because no sampled maker prints a surge, so it is the top of Champion's starting band. A generator has to cover that starting figure for a moment and the running figure after. Motors draw far more for the first second than once running.