How many watts does a heat pump use?

A heat pump is rated 3,456 W on the nameplate, the median of 5 sampled models. Champion's generator chart lists 3,000 to 3,500 W running. Sizing uses 6,000 W to start: the top of Champion's starting band, as no maker prints one. The smallest size that covers it alone is 5,500 W.

Heat pump figures

Heat pump: draw, starting watts and amps Checked on
Figure Value Where it comes from
Rated draw (nameplate) 3,456 W Median of 5 sampled models: printed watts, or printed amps x 240 V. A nameplate figure is a maximum rating.
Typical running (generator maker's chart) 3,000 to 3,500 W Champion generator wattage chart
Starting (generator maker's chart) 5,000 to 6,000 W Champion generator wattage chart
Inrush (LRA x 240 V) 22,440 W Highest locked rotor amps on the sampled sheets times the voltage. A split-second stalled-rotor figure; not used for sizing.
Starting watts for sizing 6,000 W Used because no sampled maker prints a surge, so it is the top of Champion's starting band.
Amps at 240 V 14.4 A Rated draw divided by 240 V.

What was sampled: 2 to 3 ton split-system heat pump outdoor unit, 208/230 V single phase, single-stage, R-454B or R-32.

The models we sampled

Each row is one real model and the figure its maker prints. Computed watts are printed watts, or printed amps times 240 V when the maker prints amps only.

Heat pump models sampled Checked on
Printed as, document, checked
Goodman GLZS4BA2410 8.2 not published 41.2 1,968 RLA, goodmanmfg.com, checked
Goodman GLZS4BA3610 16.4 not published 88 3,936 RLA, goodmanmfg.com, checked
Carrier 27SCA5 size 36 14.4 not published 86 3,456 COMPR RLA, shareddocs.com, checked
Lennox ML14KP1-024-230 10.3 not published 60.2 2,472 Compressor Rated load amps, lennox.com, checked
Lennox ML14KP1-036-230 16.7 not published 93.5 4,008 Compressor Rated load amps, lennox.com, checked

The generator you need

The smallest listed size that covers 3,456 W running and 6,000 W starting on its own is 5,500 W. It runs on 240 V, so the generator needs a 240 V outlet.

The smallest current generators in our data that run it alone:

Add it to the calculator with other appliances

Will a 2,000 to 7,500 watt generator run it?

Each size is treated as its own running watts, with a starting figure from the median surge of current generators that size. Each question links to the full list for that size.

Heat pump on four generator sizes
Question Generator running W Generator starting W Answer
Will a 2,000 watt generator run a heat pump? 2,000 2,545 No, too many running watts
Will a 3,500 watt generator run a heat pump? 3,500 4,375 No, cannot start it
Will a 5,000 watt generator run a heat pump? 5,000 5,500 No, cannot start it
Will a 7,500 watt generator run a heat pump? 7,500 9,388 Yes, with a 240 V outlet

With other appliances on a 3,500 W generator

Each row adds one more appliance. On this page a 3,500 W generator supplies 3,500 W running and 4,375 W starting.

Heat pump with other appliances on a 3,500 W generator
Running at once Running total W Peak at the largest start W Runs
Heat pump 3,456 6,000 No, cannot start it
Heat pump + LED lights 3,465 6,009 No, cannot start it
Heat pump + LED lights + phone charger 3,485 6,029 No, cannot start it
Heat pump + LED lights + phone charger + TV 3,704 6,248 No, too many running watts
Heat pump + LED lights + phone charger + TV + refrigerator 4,484 7,028 No, too many running watts

Every appliance on one chart

Sources

Where each Heat pump value comes from
Spec Value Printed as Document Checked
Goodman GLZS4BA2410: rated amps 8.2 A RLA goodmanmfg.com (spec sheet pdf)
Goodman GLZS4BA2410: locked rotor amps 41.2 A LRA goodmanmfg.com (spec sheet pdf)
Goodman GLZS4BA3610: rated amps 16.4 A RLA goodmanmfg.com (spec sheet pdf)
Goodman GLZS4BA3610: locked rotor amps 88 A LRA goodmanmfg.com (spec sheet pdf)
Carrier 27SCA5 size 36: rated amps 14.4 A COMPR RLA shareddocs.com (spec sheet pdf)
Carrier 27SCA5 size 36: locked rotor amps 86 A COMPR LRA shareddocs.com (spec sheet pdf)
Lennox ML14KP1-024-230: rated amps 10.3 A Compressor Rated load amps lennox.com (spec sheet pdf)
Lennox ML14KP1-024-230: locked rotor amps 60.2 A Locked rotor amps lennox.com (spec sheet pdf)
Lennox ML14KP1-036-230: rated amps 16.7 A Compressor Rated load amps lennox.com (spec sheet pdf)
Lennox ML14KP1-036-230: locked rotor amps 93.5 A Locked rotor amps lennox.com (spec sheet pdf)

Questions people ask

How many watts does a heat pump use?

The 5 models we sampled print a median of 3,456 W on the nameplate. A nameplate figure is the maximum the maker rates, not the average while running. The Champion generator chart lists 3,000 to 3,500 W as typical running watts. Plan for 6,000 W when it starts.

How many amps does a heat pump draw?

At 240 V, 3,456 W works out to 14.4 A. That is the median nameplate draw divided by 240 V. A heat pump draws from a 240 V circuit, so a generator needs a 240 V outlet to run it. Locked rotor amps put the split-second inrush near 22,440 W, a figure not used for sizing.

What size generator does a heat pump need?

The smallest listed size that covers a heat pump on its own is 5,500 W. That covers 3,456 W running and 6,000 W starting. Anything else running at once adds to that. The smallest current generator in our data that runs it alone is the Champion 6500W Dual Fuel Inverter 201532 at 5,250 W running.

How many watts does a heat pump need to start?

We size a heat pump at 6,000 W to start, because no sampled maker prints a surge, so it is the top of Champion's starting band. A generator has to cover that starting figure for a moment and the running figure after. Motors draw far more for the first second than once running.

Page data checked on