A central AC (4 ton) is rated 5,376 W on the nameplate, the median of 5 sampled models. Champion's generator chart lists 4,000 to 5,000 W running. Sizing uses 8,000 W to start: the top of Champion's starting band, as no maker prints one. The smallest size that covers it alone is 6,500 W.
| Figure | Value | Where it comes from |
|---|---|---|
| Rated draw (nameplate) | 5,376 W | Median of 5 sampled models: printed watts, or printed amps x 240 V. A nameplate figure is a maximum rating. |
| Typical running (generator maker's chart) | 4,000 to 5,000 W | Champion generator wattage chart |
| Starting (generator maker's chart) | 6,500 to 8,000 W | Champion generator wattage chart |
| Inrush (LRA x 240 V) | 30,648 W | Highest locked rotor amps on the sampled sheets times the voltage. A split-second stalled-rotor figure; not used for sizing. |
| Starting watts for sizing | 8,000 W | Used because no sampled maker prints a surge, so it is the top of Champion's starting band. |
| Amps at 240 V | 22.4 A | Rated draw divided by 240 V. |
What was sampled: 4 ton (48,000 Btu/h) split-system outdoor condensing unit, 208/230 V single phase, single-stage, R-454B or R-32.
Each row is one real model and the figure its maker prints. Computed watts are printed watts, or printed amps times 240 V when the maker prints amps only.
| Printed as, document, checked | ||||||
|---|---|---|---|---|---|---|
| Goodman | GLXS4BA4810 | 19.4 | not published | 127.7 | 4,656 | RLA, goodmanmfg.com, checked |
| Trane | N5AC5048A1000A | 17.3 | not published | 126 | 4,152 | R.L. Amps, elibrary.tranetechnologies.com, checked |
| Carrier | 26SCA5 size 48 | 22.4 | not published | 126 | 5,376 | COMPR RLA, shareddocs.com, checked |
| Lennox | ML14KC1-048 | 22.4 | not published | 126 | 5,376 | Compressor Rated load amps, lennox.com, checked |
| Rheem | RA14AY48AJ1NA | 22.4 | not published | 126 | 5,376 | Compressor Rated load amps, files.myrheem.com, checked |
The smallest listed size that covers 5,376 W running and 8,000 W starting on its own is 6,500 W. It runs on 240 V, so the generator needs a 240 V outlet.
The smallest current generators in our data that run it alone:
Champion Power Equipment, Dual fuel inverter
Generac, Open frame
Generac, Open frame
Each size is treated as its own running watts, with a starting figure from the median surge of current generators that size. Each question links to the full list for that size.
| Question | Generator running W | Generator starting W | Answer |
|---|---|---|---|
| Will a 2,000 watt generator run a central AC (4 ton)? | 2,000 | 2,545 | No, too many running watts |
| Will a 3,500 watt generator run a central AC (4 ton)? | 3,500 | 4,375 | No, too many running watts |
| Will a 5,000 watt generator run a central AC (4 ton)? | 5,000 | 5,500 | No, too many running watts |
| Will a 7,500 watt generator run a central AC (4 ton)? | 7,500 | 9,388 | Yes, with a 240 V outlet |
Each row adds one more appliance. On this page a 3,500 W generator supplies 3,500 W running and 4,375 W starting.
| Running at once | Running total W | Peak at the largest start W | Runs |
|---|---|---|---|
| Central AC (4 ton) | 5,376 | 8,000 | No, too many running watts |
| Central AC (4 ton) + LED lights | 5,385 | 8,009 | No, too many running watts |
| Central AC (4 ton) + LED lights + phone charger | 5,405 | 8,029 | No, too many running watts |
| Central AC (4 ton) + LED lights + phone charger + TV | 5,624 | 8,248 | No, too many running watts |
| Central AC (4 ton) + LED lights + phone charger + TV + refrigerator | 6,404 | 9,028 | No, too many running watts |
2,472 W running 4,500 W starting
3,240 W running 6,000 W starting
750 W running 1,600 W starting
3,456 W running 6,000 W starting
1,035 W running 2,400 W starting
445 W running 1,200 W starting
710 W running 2,400 W starting
| Spec | Value | Printed as | Document | Checked |
|---|---|---|---|---|
| Goodman GLXS4BA4810: rated amps | 19.4 A | RLA | goodmanmfg.com (spec sheet pdf) | |
| Goodman GLXS4BA4810: locked rotor amps | 127.7 A | LRA | goodmanmfg.com (spec sheet pdf) | |
| Trane N5AC5048A1000A: rated amps | 17.3 A | R.L. Amps | elibrary.tranetechnologies.com (spec sheet pdf) | |
| Trane N5AC5048A1000A: locked rotor amps | 126 A | L.R. Amps | elibrary.tranetechnologies.com (spec sheet pdf) | |
| Carrier 26SCA5 size 48: rated amps | 22.4 A | COMPR RLA | shareddocs.com (spec sheet pdf) | |
| Carrier 26SCA5 size 48: locked rotor amps | 126 A | COMPR LRA | shareddocs.com (spec sheet pdf) | |
| Lennox ML14KC1-048: rated amps | 22.4 A | Compressor Rated load amps | lennox.com (spec sheet pdf) | |
| Lennox ML14KC1-048: locked rotor amps | 126 A | Locked rotor amps | lennox.com (spec sheet pdf) | |
| Rheem RA14AY48AJ1NA: rated amps | 22.4 A | Compressor Rated load amps | files.myrheem.com (spec sheet pdf) | |
| Rheem RA14AY48AJ1NA: locked rotor amps | 126 A | Locked rotor amps | files.myrheem.com (spec sheet pdf) |
The 5 models we sampled print a median of 5,376 W on the nameplate. A nameplate figure is the maximum the maker rates, not the average while running. The Champion generator chart lists 4,000 to 5,000 W as typical running watts. Plan for 8,000 W when it starts.
At 240 V, 5,376 W works out to 22.4 A. That is the median nameplate draw divided by 240 V. A central AC (4 ton) draws from a 240 V circuit, so a generator needs a 240 V outlet to run it. Locked rotor amps put the split-second inrush near 30,648 W, a figure not used for sizing.
The smallest listed size that covers a central AC (4 ton) on its own is 6,500 W. That covers 5,376 W running and 8,000 W starting. Anything else running at once adds to that. The smallest current generator in our data that runs it alone is the Champion 8500W Wireless Start Dual Fuel Inverter 201536 at 6,500 W running.
We size a central AC (4 ton) at 8,000 W to start, because no sampled maker prints a surge, so it is the top of Champion's starting band. A generator has to cover that starting figure for a moment and the running figure after. Motors draw far more for the first second than once running.