Predator 5000 Portable Generator
Predator, Open frame
- Running
- 4,000 W
- Starting
- 5,000 W
- Weight
- 110 lb
A central AC (2 ton) is rated 2,472 W on the nameplate, the median of 5 sampled models. Champion's generator chart lists 2,000 to 2,500 W running. Sizing uses 4,500 W to start: the top of Champion's starting band, as no maker prints one. The smallest size that covers it alone is 4,000 W.
| Figure | Value | Where it comes from |
|---|---|---|
| Rated draw (nameplate) | 2,472 W | Median of 5 sampled models: printed watts, or printed amps x 240 V. A nameplate figure is a maximum rating. |
| Typical running (generator maker's chart) | 2,000 to 2,500 W | Champion generator wattage chart |
| Starting (generator maker's chart) | 3,500 to 4,500 W | Champion generator wattage chart |
| Inrush (LRA x 240 V) | 16,080 W | Highest locked rotor amps on the sampled sheets times the voltage. A split-second stalled-rotor figure; not used for sizing. |
| Starting watts for sizing | 4,500 W | Used because no sampled maker prints a surge, so it is the top of Champion's starting band. |
| Amps at 240 V | 10.3 A | Rated draw divided by 240 V. |
What was sampled: 2 ton (24,000 Btu/h) split-system outdoor condensing unit, 208/230 V single phase, single-stage, R-454B or R-32.
Each row is one real model and the figure its maker prints. Computed watts are printed watts, or printed amps times 240 V when the maker prints amps only.
| Printed as, document, checked | ||||||
|---|---|---|---|---|---|---|
| Goodman | GLXS4BA2410 | 8.2 | not published | 41.2 | 1,968 | RLA, goodmanmfg.com, checked |
| Trane | N5AC5024A1000A | 10.9 | not published | 60 | 2,616 | R.L. Amps, elibrary.tranetechnologies.com, checked |
| Carrier | 26SCA5 size 24 | 10.3 | not published | 60.2 | 2,472 | COMPR RLA, shareddocs.com, checked |
| Lennox | ML14KC1-024 | 10.3 | not published | 60.2 | 2,472 | Compressor Rated load amps, lennox.com, checked |
| Rheem | RA14AY24AJ1NA | 12.7 | not published | 67 | 3,048 | Compressor Rated load amps, files.myrheem.com, checked |
The smallest listed size that covers 2,472 W running and 4,500 W starting on its own is 4,000 W. It runs on 240 V, so the generator needs a 240 V outlet.
The smallest current generators in our data that run it alone:
Predator, Open frame
Predator, Open frame
Champion Power Equipment, Open frame
Each size is treated as its own running watts, with a starting figure from the median surge of current generators that size. Each question links to the full list for that size.
| Question | Generator running W | Generator starting W | Answer |
|---|---|---|---|
| Will a 2,000 watt generator run a central AC (2 ton)? | 2,000 | 2,545 | No, too many running watts |
| Will a 3,500 watt generator run a central AC (2 ton)? | 3,500 | 4,375 | No, cannot start it |
| Will a 5,000 watt generator run a central AC (2 ton)? | 5,000 | 5,500 | Yes, with a 240 V outlet |
| Will a 7,500 watt generator run a central AC (2 ton)? | 7,500 | 9,388 | Yes, with a 240 V outlet |
Each row adds one more appliance. On this page a 3,500 W generator supplies 3,500 W running and 4,375 W starting.
| Running at once | Running total W | Peak at the largest start W | Runs |
|---|---|---|---|
| Central AC (2 ton) | 2,472 | 4,500 | No, cannot start it |
| Central AC (2 ton) + LED lights | 2,481 | 4,509 | No, cannot start it |
| Central AC (2 ton) + LED lights + phone charger | 2,501 | 4,529 | No, cannot start it |
| Central AC (2 ton) + LED lights + phone charger + TV | 2,720 | 4,748 | No, cannot start it |
| Central AC (2 ton) + LED lights + phone charger + TV + refrigerator | 3,500 | 5,528 | No, cannot start it |
3,240 W running 6,000 W starting
5,376 W running 8,000 W starting
750 W running 1,600 W starting
3,456 W running 6,000 W starting
1,035 W running 2,400 W starting
445 W running 1,200 W starting
710 W running 2,400 W starting
| Spec | Value | Printed as | Document | Checked |
|---|---|---|---|---|
| Goodman GLXS4BA2410: rated amps | 8.2 A | RLA | goodmanmfg.com (spec sheet pdf) | |
| Goodman GLXS4BA2410: locked rotor amps | 41.2 A | LRA | goodmanmfg.com (spec sheet pdf) | |
| Trane N5AC5024A1000A: rated amps | 10.9 A | R.L. Amps | elibrary.tranetechnologies.com (spec sheet pdf) | |
| Trane N5AC5024A1000A: locked rotor amps | 60 A | L.R. Amps | elibrary.tranetechnologies.com (spec sheet pdf) | |
| Carrier 26SCA5 size 24: rated amps | 10.3 A | COMPR RLA | shareddocs.com (spec sheet pdf) | |
| Carrier 26SCA5 size 24: locked rotor amps | 60.2 A | COMPR LRA | shareddocs.com (spec sheet pdf) | |
| Lennox ML14KC1-024: rated amps | 10.3 A | Compressor Rated load amps | lennox.com (spec sheet pdf) | |
| Lennox ML14KC1-024: locked rotor amps | 60.2 A | Locked rotor amps | lennox.com (spec sheet pdf) | |
| Rheem RA14AY24AJ1NA: rated amps | 12.7 A | Compressor Rated load amps | files.myrheem.com (spec sheet pdf) | |
| Rheem RA14AY24AJ1NA: locked rotor amps | 67 A | Locked rotor amps | files.myrheem.com (spec sheet pdf) |
The 5 models we sampled print a median of 2,472 W on the nameplate. A nameplate figure is the maximum the maker rates, not the average while running. The Champion generator chart lists 2,000 to 2,500 W as typical running watts. Plan for 4,500 W when it starts.
At 240 V, 2,472 W works out to 10.3 A. That is the median nameplate draw divided by 240 V. A central AC (2 ton) draws from a 240 V circuit, so a generator needs a 240 V outlet to run it. Locked rotor amps put the split-second inrush near 16,080 W, a figure not used for sizing.
The smallest listed size that covers a central AC (2 ton) on its own is 4,000 W. That covers 2,472 W running and 4,500 W starting. Anything else running at once adds to that. The smallest current generator in our data that runs it alone is the Predator 5000 Portable Generator at 4,000 W running.
We size a central AC (2 ton) at 4,500 W to start, because no sampled maker prints a surge, so it is the top of Champion's starting band. A generator has to cover that starting figure for a moment and the running figure after. Motors draw far more for the first second than once running.