How to size a standby generator

To size a standby generator, list the loads you want backed up, decide whether everything connects at once or a load management system holds big loads off, and check the generator's rating on your fuel, since most make less power on propane than on natural gas. An electrician then confirms the size with a code load calculation.

Updated

Step 1: list the loads

Walk the panel. Every double-pole breaker is a 240 V load and a candidate for the biggest draws in the house: central air or a heat pump, an electric water heater, an electric range, an electric dryer, a well pump, an EV charger. Note them first, then the 120 V circuits you'd want: fridge, freezer, furnace blower, sump pump, lights, outlets, the router.

For each, find running watts and, for motors, starting watts. The calculator does the sum with figures from manufacturer spec sheets, and each appliance page links the sheets it used.

Example: a refrigerator, LED lights, a phone charger and a TV
Appliance RunningW Starting for sizingW
Refrigerator 780 W 1,200 W (chart)
LED lights 9 W 9 W
Phone charger 20 W 20 W
TV 219 W 219 W
Running total
1,028 W
Starting peak
1,448 W
Recommended size
2,000 W

The running total divided by the continuous-load factor of 0.8 is 1,285 W. The starting peak is the running total plus the largest single surge. The larger of the two, rounded up to the next listed size, is the recommendation. Starting watts for Refrigerator come from the generator maker's chart, because the sampled spec sheets print no surge figure.

Size your own list in the calculator

The biggest single starting surge in most houses is the central AC or heat pump compressor. Look at the 2 ton, 3 ton and 4 ton central AC pages, or the heat pump page, and compare with the data plate on your own outdoor unit. If the plate lists locked rotor amps (LRA), that's the surge figure to use.

Step 2: whole house, managed, or essentials

This choice changes the generator size more than anything else.

Whole house with no management. The generator covers everything that can connect at once. Under the National Electrical Code, an automatic transfer that connects the full load needs a generator able to supply that full load, calculated under Article 220 or another approved method [11].

Whole house with load management. Every circuit is connected, but an energy management system keeps the big loads off until there's capacity. The code then requires the generator to cover the maximum load the system will allow [11]. This is how a mid-size standby unit backs up a house with central air.

Essentials. A smaller transfer switch or a subpanel feeds the circuits you chose. Smallest generator, lowest cost, and nothing else runs.

Step 3: choose the fuel and read the right rating

Home standby generators run on natural gas or propane. Most publish two running ratings, one per fuel. Natural gas holds about 1,000 Btu per cubic foot, and propane vapor about 2,500 Btu per cubic foot, so engines are tuned differently for each and the output differs.

Read the rating for your fuel, not the headline number. The Generac Guardian 22 kW, for example, is rated at 19,500 W on natural gas and 22,000 W on propane. The Champion aXis 14 kW is rated at 12,500 W on natural gas and 14,000 W on propane.

The table below lists every standby model on the site with both ratings and the fuel use at half and full load, each from the maker's spec sheet.

Home standby generators Checked on
Briggs & Stratton PowerProtect 13 kW 11.5 13 119 62 ft3/h 315 7 years parts, labor and travel for emergency stationary use (generator, USA and Canada); enclosure 1 year surface rust, 3 years rust through $4,460
Briggs & Stratton PowerProtect 18 kW 18 18 not published not published 465 7-year comprehensive limited warranty $5,746
Briggs & Stratton PowerProtect 22 kW 22 22 194 87 ft3/h 465 7 years parts, labor and travel (generator, domestic and Canada); 7 years or 1,000 hours for non-emergency use; enclosure 1 year surface rust, 3 years rust through $6,037
Briggs & Stratton PowerProtect 26 kW 24 26 206 94 ft3/h 540 7 years parts, labor and travel (generator, domestic and Canada); 7 years or 1,000 hours for non-emergency use; enclosure 1 year surface rust, 3 years rust through not published
Briggs & Stratton PowerProtect+ 18 kW 18 18 176 77 ft3/h 490 7 years parts, labor and travel for emergency stationary use (generator, USA and Canada); 7 years or 1,000 hours for non-emergency stationary use; enclosure 1 year surface rust, 3 years rust through $6,135
Briggs & Stratton PowerProtect+ 22 kW 22 22 194 87 ft3/h 490 7 years parts, labor and travel for emergency stationary use (generator, USA and Canada); 7 years or 1,000 hours for non-emergency stationary use; enclosure 1 year surface rust, 3 years rust through $6,532
Briggs & Stratton PowerProtect+ 26 kW 24 26 206 94 ft3/h 545 7 years parts, labor and travel for emergency stationary use (generator, USA and Canada); 7 years or 1,000 hours for non-emergency stationary use; enclosure 1 year surface rust, 3 years rust through $7,336
Champion aXis 14 kW 12.5 14 116.5 1.6 438.7 10 years or 2,000 hours, whichever occurs first: parts, labor and mileage in years 1 and 2, parts only in years 3 through 10 not published
Champion aXis 22 kW 19.8 22 173.4 2 590.4 10 years or 2,000 hours, whichever occurs first: parts, labor and mileage in years 1 and 2, parts only in years 3 through 10 not published
Generac Guardian 10 kW 9 10 101 36 ft3/h 338 5 years or 2,000 hours, whichever occurs first: parts, labor and limited travel in years 1 and 2, parts only in year 3, engine short block and alternator only in years 4 and 5 not published
Generac Guardian 14 kW 14 14 195 65 ft3/h 385 5 years or 2,000 hours, whichever occurs first: parts, labor and limited travel in years 1 and 2, parts only in year 3, engine short block and alternator only in years 4 and 5 not published
Generac Guardian 18 kW 17 18 169 62 ft3/h 420 5 years or 2,000 hours, whichever occurs first: parts, labor and limited travel in years 1 and 2, parts only in year 3, engine short block and alternator only in years 4 and 5 not published
Generac Guardian 22 kW 19.5 22 228 92 ft3/h 466 5 years or 2,000 hours, whichever occurs first: parts, labor and limited travel in years 1 and 2, parts only in year 3, engine short block and alternator only in years 4 and 5 not published
Generac Guardian 24 kW 21 24 203 92 ft3/h 455 5 years or 2,000 hours, whichever occurs first: parts, labor and limited travel in years 1 and 2, parts only in year 3, engine short block and alternator only in years 4 and 5 not published
Generac Guardian 26 kW 22.5 26 188 75 ft3/h 518 5 years or 2,000 hours, whichever occurs first: parts, labor and limited travel in years 1 and 2, parts only in year 3, engine short block and alternator only in years 4 and 5 not published
Kohler 10RESV 9 10 120 52 ft3/h 428 5 years or 2,000 hours, premium limited standby warranty covering parts, labor and travel for the full period $3,946
Kohler 12RESV 11 12 128 57 ft3/h 433 5 years or 2,000 hours, premium limited standby warranty covering parts, labor and travel for the full period $4,384
Kohler 14RCA 12 14 124 60 ft3/h 452.5 5 years or 2,000 hours, premium limited standby warranty covering parts, labor and travel for the full period $5,098
Kohler 20RCA 18 20 161 82 ft3/h 567.5 5 years or 2,000 hours, premium limited standby warranty covering parts, labor and travel for the full period $6,016
Kohler 26RCA 24 26 180 85 ft3/h 670 5 years or 2,000 hours, premium limited standby warranty covering parts, labor and travel for the full period $7,546

Step 4: check the gas supply

A standby generator needs enough gas flow at the right pressure. On natural gas, that means the meter and the pipe run from the meter to the generator have to carry the generator's full-load consumption on top of the furnace, water heater and range. Some houses need a larger meter from the utility.

On propane, the tank has to hold enough for the outage you plan for and vaporize fast enough in cold weather. The fuel consumption figures in the table above, read from each spec sheet, are what a plumber or propane supplier uses to size the pipe or tank. The gas vs propane guide covers the trade-offs.

Step 5: confirm with a load calculation

Your list gets you close. The final size comes from the electrician's load calculation, which the inspector reviews with the permit. Ask for it in writing, along with:

  • the transfer switch rating and whether it's service rated
  • which loads are managed and in what order they shed
  • the generator's rating on your fuel, not the other fuel
  • the placement and clearances from the maker's installation manual

Placement rules come from the manufacturer's manual and local code, and they cover distance from windows, doors, vents and other openings. Don't let an installer guess them.

Sizing mistakes to avoid

Sizing to the main breaker. A 200 A panel doesn't need a generator that can carry 200 A. See the 200 amp service guide.

Reading the natural gas rating when you have propane. Or the reverse. The gap can move you a full size.

Forgetting the AC surge. A generator that runs the AC fine once it's going can still fail to start it. Check starting capability, or ask about a soft starter for the compressor.

Oversizing "to be safe." A bigger unit costs more, burns more fuel at the same load, and runs lightly loaded most of its life. Load management usually buys more than extra kilowatts.

Standby or portable?

If you only need essentials and can wheel a generator out during an outage, a portable unit with an interlock or transfer switch costs much less. The portable vs standby guide compares them, and the standby generators page lists every standby model on the site with its source documents.

FAQ

How do I calculate what size standby generator I need?

List your loads, add running watts for what runs at once, and add the biggest motor surge. Then decide whether a load management system will hold big loads off. An electrician confirms the size with a code load calculation. The calculator on this page gives you a starting figure.

Why is a standby generator rated lower on propane?

Propane and natural gas carry different energy per cubic foot and burn differently, so makers tune the engine for each and publish a rating for each fuel. Most standby units list a different number for each. Always size from the rating for the fuel you'll actually use.

Do I need a whole-house generator or will essentials do?

Essentials cover the fridge, heat, water and lights for much less money. Whole-house backup suits people who want central air, cooking and laundry without managing anything. Load management sits between: every circuit connected, with big loads held off until there's room on the generator.

Who should size and install a standby generator?

A licensed electrician does the load calculation and installs the transfer switch, and a licensed plumber or gas fitter sizes and runs the gas line. Most areas require permits and an inspection. The generator maker's installation manual sets the clearances and the gas pressure the unit needs.