kW to amps calculator

To convert kW to amps, multiply the kW by 1,000 and divide by the volts times the power factor. With a power factor of 1, a 10 kW load draws 41.67 A on each hot leg at 240 V split phase, and 83.33 A at 120 V single phase.

Phase
Set by the phase choice; type another voltage if yours differs.
Defaults to 1, where watts and volt-amperes are equal. Enter the figure from your equipment if it prints one.
Result83.33A

10 kW at 120 V and a power factor of 1 draws 83.33 A. Single phase, 120 V: one hot leg and neutral.

The smallest listed generator size at or above 10,000 W running is 10,000 W.

The formula

amps = kW x 1,000 / (volts x power factor)

Single phase uses one hot leg and neutral, 120 V on US generators. Split phase puts a 240 V load across both hot legs, and the amps shown are per leg. A power factor of 1 gives the amps for the watts as stated; a lower power factor means more amps for the same watts.

At each listed generator size

Amps at each listed generator size, power factor 1
Generator size kW At 120 V A At 240 V, per leg A
2 16.67 8.33
2.5 20.83 10.42
3 25 12.5
3.5 29.17 14.58
4 33.33 16.67
4.5 37.5 18.75
5 41.67 20.83
5.5 45.83 22.92
6 50 25
6.5 54.17 27.08
7 58.33 29.17
7.5 62.5 31.25
8 66.67 33.33
9 75 37.5
10 83.33 41.67
12 100 50
15 125 62.5
20 166.67 83.33
22 183.33 91.67
24 200 100
26 216.67 108.33